Availability: | |
---|---|
Quantity: | |
HSLH-JZ
REPS
Product Description
Halogen-free signal cable with improved properties under fire, suitable for different applications in control and measuring circuits, in industry and facilities where human lives or valuable property need to be protected against damages caused by fire. Suitable for fixed, same as for mobile installation, but free of mechanical stress; for dry and damp environment, not for outdoor application. Resistant to majority of most frequently used oils.
Advantages:
• Halogen-free, no release of toxic or corrosive gases under fire
• Reduced smoke occurrence under fire
• No flame propagation in vertical cable bundle
Technical Data
Technical data Temperature range:
• During installation: -5 °C up to +50 °C
• Fixed installed: -20 °C up to +70 °C
• Maximal operating temperature: 70 °C
• At short circuit of max. 5 s: up to 150 °C
Nominal voltage: U0 /U = 300/500 V
Test voltage: 2000 V
Minimal inner bending radius: (D = external cable diameter)
• Fixed installation: 4D
• Mobile installation: 15D
Properties under fire:
Flame retardant: acc. to IEC 60332-1 / EN 60332-1 (earlier EN 50265-2-1) / VDE 0482-332-1
No flame propagation in vertical cable bundle: acc. to IEC 60332-3 / EN 50266-1,-2 / DIN VDE 0482-266-2-4 (same as DIN VDE 0472 part 804 test method C)
Halogen-free: acc. to IEC 60754-1 / EN 50267 -1,-2-1 / DIN VDE 0482-267 -1,-2-1 (same as DIN VDE 0472 part 815) Non-corrosive combustion gases: acc. to IEC 60754-2 / EN 50267-2-2 / DIN VDE 0482-267-2-2 (same as DIN VDE 0472 part 813)
Low smoke density: acc. to IEC 61034-2 / EN 61034-2 (earlier EN 50268) / DIN VDE 0482-1034-2 (same as DIN VDE 0472 part 816) - visibility > 70%
Construction
1. Conductor: bare copper conductor, fine wired, stranded in layers, class 5 acc. to. HRN HD 383 / IEC 60228 / DIN VDE 0295
2. Insulation: cross-linked halogen-free polyolefin polymer \
• Concentrically stranded cores
3. Sheath: cross-linked halogen-free polyolefin polymer
• Sheath colour: light grey (for inst. RAL 7001 or RAL 7035)
Core colour marking:
• Acc. to HRN HD 308 S2 / VDE 0293-308
Dimensions